beautypg.com

Chapter 8, Using the scanport capabilities, Chapter objectives – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual

Page 125: Understanding the logic input sts parameter, Scanport definition, Chapter

background image

Chapter

8

Using the SCANport Capabilities

Chapter Objectives

Chapter 8 provides information for changing the default configuration
to customize the way SCANport works for you.

Understanding the Logic Input
Sts Parameter

Logic Input Sts (parameter 14) shows which functions are currently
executing. To use SCANport effectively, you need to understand how
Logic Input Sts works.

Logic Input Sts has the following bits:

SCANport Definition

Serial Communications devices such as the Human Interface Module
that are directly mounted on the IMPACT drive are identified as
SCANport Device 1. Remote communication devices such as a HIM,
GPT etc. are identified as Device 2 and up (depending on the amount
of control devices connected to the Drive).

This topic:

Starts on page:

Understanding the Logic Input Sts parameter

8-1

Configuring the SCANport controls

8-3

Setting the SCANport faults

8-7

Using the SCANport I/O image

8-8

Setting the analog I/O parameters

8-14

file:

Monitor

group:

Drive/Inv Status

This bit:

Identifies this function:

This bit:

Identifies this function:

0

Normal Stop

8

Coast Stop

1

Start

9

Ramp Disable

2

Jog1

10

Flux Enable

3

Clear Fault

11

Process Trim Enable

4

Forward

12

Speed Ref A

5

Reverse

13

Speed Ref B

6

Jog2

14

Speed Ref C

7

Current Limit Stop

15

Reset Drive