8-6
Using the SCANport Capabilities
For each of these parameters, each bit represents a device:
Masking Control Functions
You can also mask control functions. This lets you enable or disable a
control function for all or some of the devices.
Important: You cannot mask the stop command. Any device
attached to the 1336 IMPACT drive can stop the drive at any time.
To set a mask for a control function, you can use the following
parameters:
For each of these parameters, each bit represents a device:
If this bit is set
(for low):
Or if this bit is set
(for high):
Then, the owner is:
0
8
L Option
1
9
SCANport device 1
2
10
SCANport device 2
3
11
SCANport device 3
4
12
SCANport device 4
5
13
SCANport device 5
6
14
SCANport device 6
7
15
Logic Cmd Input (parameter 197)
The SCANport device number is determined by the SCANport
connection it is plugged into.
mask = 1
mask = 0
Control Function
Control
Input
file:
Interface/Comm
group:
SCANport Config
To set a mask to control
this function:
Set the appropriate bit in
the high/low byte:
Use this
parameter:
Control which ports can accept the
control functions
124
Issue forward/reverse commands
High
125
Issue a start command
High
126
Issue a jog command
Low
126
Select an alternate reference or preset
speed
Low
125
Generate a clear fault command
High
127
Reset drive
Low
127
This bit (for
low):
Or this bit (for
high):
Represents:
0
8
L Option
1
9
SCANport device 1
2
10
SCANport device 2
3
11
SCANport device 3
4
12
SCANport device 4
5
13
SCANport device 5
6
14
SCANport device 6
7
15
Logic Cmd Input (parameter 197)