23 warning select 2, 24 absolute overspd, 25 motor stall time – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 215: 26 motor overload, 27 line undervolts
Parameters
11-17
23
Warning Select 2
Use Warning Select 2 to specify how the drive should handle
certain conditions. Each bit matches the bit definitions of Fault
Select 2 (parameter 22). If you set a bit to 1 and the
corresponding bit in Fault Select 2 is clear (0), the drive reports a
warning when that condition occurs. If both corresponding bits in
Fault Select 2 and Warning Select 2 are 0, the drive ignores the
condition when it occurs.
The bits are defined as follows:
Parameter number
File:group
Fault Setup:Fault Config
Parameter type
linkable destination
Display
bits
Factory default
10100000.00001010
Minimum value
00000000.00000000
Maximum value
11111111.11111111
Conversion
1 = 1
Refer to Chapter 12, Troubleshooting, for additional information.
Bit
Description
0
SpdFdbk Loss
A loss of feedback occurred.
1
InvOvtmp Pnd
An inverter overtemp is pending.
2
Reserved
Leave 0.
3
MtrOvld Pend
A motor overload is pending (I
2
T).
4
MtrOvld Trip
Motor overload trip (I
2
T)
Bit
Description
5
Mtr Stall
The motor stalled.
6
Ext Fault In
The ext input is open.
7 – 8
Reserved
Leave 0.
9
Param Limit
A parameter is out of limits
10
Math Limit
A math limit occurred.
Bit
Description
11 – 12 Reserved
Leave 0.
13
InvOvld Pend
An inverter overload is pending
(IT).
14
Reserved
Leave 0.
15
InvOvld Trip
Inverter overload trip (IT)
24
Absolute Overspd
Enter the incremental speed above Fwd Speed Limit
(parameter 41) or below Rev Speed Limit (parameter 40) that is
allowable before the drive indicates its speed is out of range, an
Absolute Overspd fault (fault number 03025).
Parameter number
File:group
Fault Setup:Fault Limits
Parameter type
linkable destination
Display
x.x rpm
Factory default
base motor speed x 0.1 rpm
Minimum value
0.0 rpm
Maximum value
base motor speed rpm
Conversion
4096 = 100% overspeed
25
Motor Stall Time
Enter the length of time that the drive must be in current limit and
at zero speed before the drive indicates a Mtr Stall fault (fault
number 01053). You can use bit 5 of Fault Select 2
(parameter 22) and Warning Select 2 (parameter 23) to configure
how the drive should report a Mtr Stall fault.
Parameter number
File:group
Fault Setup:Fault Limits
Parameter type
linkable destination
Display
x.x seconds
Factory default
1.0 seconds
Minimum value
0.1 seconds
Maximum value
3276.7 seconds
Conversion
10 = 1.0
26
Motor Overload %
Enter the level of current that will cause a Motor Overld Trp fault
(fault number 01052) after 60 seconds. You can use bit 4 of Fault
Select 2 (parameter 22) and Warning Select 2 (parameter 23) to
configure how the drive should report a Motor Overld Trp.
Parameter number
File:group
Fault Setup:Fault Limits
Parameter type
linkable destination
Display
x.x%
Factory default
200.0%
Minimum value
110.0%
Maximum value
400.0%
Conversion
4096 = 100% Iq for 60 seconds
27
Line Undervolts
Enter the minimum threshold as a percentage of the line voltage
that is compared with DC Bus Voltage (parameter 84) as a check
for a bus undervoltage condition.
Parameter number
File:group
Fault Setup:Fault Limits
Parameter type
linkable destination
Display
x.x%
Factory default
61.5%
Minimum value
10.0%
Maximum value
90.0%
Conversion
1024 = 100.0%
Refer to Chapter 12, Troubleshooting, for additional information.