1language select, 2nameplate hp, 3nameplate rpm – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 208: 4nameplate amps, 5nameplate volts, 6nameplate hz

11-10
Parameters
1
Language Select
Use Language Select to choose between a primary language
and an alternate language. Select:
• 0 to choose the primary language
• 1 to choose the alternate language
Parameter number
File:group
none
Parameter type
linkable destination
Display
x
Factory default
0
Minimum value
0
Maximum value
1
Conversion
1 = 1
2
Nameplate HP
Nameplate HP contains the value of the motor horsepower that
you entered during the start up routine. This value is typically
located on the motor nameplate.
Parameter number
File:group
Motor/Inverter:Motor Nameplate
Parameter type
destination
Display
x .x hp
Factory default
30.0 hp
Minimum value
0.2 hp
Maximum value
2000.0 hp
Conversion
10 = 1.0
3
Nameplate RPM
Nameplate RPM contains the value of the motor speed that you
entered during the start up routine. This value is typically located
on the motor nameplate. This value should not be the
synchronous speed of the motor.
Parameter number
File:group
Motor/Inverter:Motor Nameplate
Parameter type
destination
Display
x rpm
Factory default
1750 rpm
Minimum value
1 rpm
Maximum value
15000 rpm
Conversion
1 = 1
4
Nameplate Amps
Nameplate Amps contains the value of the current rating of the
motor that you entered during the start up routine. This value is
typically located on the motor nameplate. The drive uses this
information to properly tune to the motor.
Parameter number
File:group
Motor/Inverter:Motor Nameplate
Parameter type
destination
Display
x.x amps
Factory default
0.2 amps
Minimum value
0.1 amps
Maximum value
calculated
Conversion
10 = 1.0
5
Nameplate Volts
Nameplate Volts contains the voltage rating of the motor that you
entered during the start up routine. This value is typically located
on the motor nameplate.
Parameter number
File:group
Motor/Inverter:Motor Nameplate
Parameter type
destination
Display
x volt
Factory default
460 volts
Minimum value
75 volts
Maximum value
575 volts
Conversion
1 = 1
6
Nameplate Hz
Nameplate Hz contains the value of the frequency rating of the
motor that you entered during the start up routine. This value is
typically located on the motor nameplate.
Parameter number
File:group
Motor/Inverter:Motor Nameplate
Parameter type
destination
Display
x.x Hz
Factory default
60.0 Hz
Minimum value
1.0 Hz
Maximum value
250.0 Hz
Conversion
10 = 1.0