4 Monitoring Functions
09.91
4.6 Listing of the alarms/alarm description
Alarm No.
AlarmText:
32
”Data format error R232C (V.24)”
Reason:
Effect:
Remedy:
– The permissible number of decades after an address is not correct
– The decimal point occurs in the wrong place
– The part programs or subroutines are not defined or completed
correctly (check heading!)
– The NC is waiting for an ”=” character, which is not defined in EIA
code.
– Data transfer is interrupted
– The last block is not stored
Check the data to be read in.
Alarm No.
Alarm Text:
33
”Different programs same no. R232C (V.24)”
Reason:
Effect:
Remedy:
Explanation:
The stored program and the program being read in, have the same
program number, but are not identical.
With block transfer: Program read in not identical with selected
program.
No data are stored
Either delete or ”RENAME” the old program
With block transfer: Enter correct program number in Automatic basic
display.
If a new program is read in which has the same program number as
one already stored, both programs are compared and alarm 33 is
displayed.
With block transfer: The received program number is compared with
the program number specified in the Automatic basic display. If the
program numbers differ from each other Alarm 33 is triggered.
Alarm No.
Alarm Text:
34
”Operator error R232C (V.24)”
Reason:
Effect:
Remedy:
Data transfer was started on the NC, but the PLC gave a second Start
signal.
No data are read in
Stop data input, and restart
Alarm No.
Alarm Text:
35
”Reader error R232C (V.24)”
Reason:
Effect:
Remedy:
Error message from Siemens tape reader
– Data transfer is interrupted
– The last block is not stored
– Restart data transfer
– If the fault reoccurs, call Service