Remote i/o communication parameters – Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual
Page 64

4–8
Communications Overview
Publication 2711-6.0
Remote I/O Communication Parameters
Remote I/O communication parameters are defined in the
Communication Setup dialog which is accessed from the Terminal
Setup dialog.
Terminal Name is stored in Project
with Catalog Number information.
PanelView 900
Remote I/O Terminal
with RS-232 Printer Port
Must match Node
Name in Tag Editor.
The table below defines Remote I/O communication parameters for
the PanelView terminal.
Remote I/O
Device
Remote I/O
Parameter
Description
Options
PLC/S anner
Type
Type of PLC controller/scanner that will
communicate with the PanelView
Remote I/O terminal.
See table on
page 4–7.
PLC/Scanner
Name
Unique name assigned to controller.
This name is also used in the Node
Name field in the Tag Editor.
User supplied
Rack Address
Unique address of PanelView terminal
on Remote I/O link.
0 – 27
octal
Pane V ew
Module Group
Module groups occupied by PanelView
terminal in the rack. The Module groups
must be contiguous.
0,1 2,3 4,5 6,7
PanelView
Terminal
Baud Rate
The baud rate of the Remote I/O link
determines the maximum cable length.
57.6K
10,000 feet
115.2K
5,000 feet
230.4K
2,500 feet
Last Chassis
Specifies whether the terminal occupies
the last module group (no higher module
groups assigned) within the rack.
Yes, No