Internal Read Only Tags
G–4
Publication 2711-6.0
ControlNet Tags
You can display the Network Update Time (NUT), UMAX Node,
SMAX Node and other data on a screen by assigning one of the
following read only tags to a display objet. You must use an ASCII
display for tags with a string data type.
Tag Name
Data Type
Description
@Read_DCNUTime
Unsigned Integer
Network Update Time (NUT) in milliseconds.
@Read_DCUMAX
Unsigned Integer
Unscheduled Maximum (UMAX) node address
@Read_DCSMAX
Unsigned Integer
Scheduled Maximum (SMAX) node address
@Read_curDCAddress
Unsigned Integer
Current Node Address
@Read_DCASANumber
String
CIP/ASA serial number of the PanelView
@Read_DCCommStatus
Unsigned Integer
Communication status number
@Read_DCFirmwareRev
String
ControlNet firmware revision number
@Read_DCNewAddress
Unsigned Integer
Terminal address to use after a reset
@Read_DCProtocol
String
Firmware build date
@Read_DCRedundancy
Unsigned Integer
LED status number. Indicates status of A and B cables.
@Read_DCScanDelay
Unsigned Integer
Scan delay in milliseconds (time between reads)
DeviceNet Tags
Tag Name
Data Type
Value Range
Description
@Read_DCB01
Unsigned Integer
0 or 1
0 = Hold in Reset, 1 = Reset and Continue Comms.
@Read_DCCommStatus
Unsigned Integer
0 to 13
0 = No connection
1 = Connection timed out.
3 = Cannot obtain Explicit–Client tag
4 = Zero length I/O message received
5 = Message overrun
11 = No network power
12 = Dup MAC failure
13 = Bus–Off interrupt occurred
@Read_DCInputSize
Unsigned Integer
0 to 64
Number of words sent to scanner from PanelView with
each I/O scan.
@Read_DCOutputSize
Unsigned Integer
0 to 64
Number of words sent to PanelView from scanner with
each I/O scan.
@Read_DCScanDelay
Unsigned Integer
0 to 65535
Delay scan of the Explicit-Client tags
@Read_DCAddress
Unsigned Integer
0 to 63
Address of PanelView on DeviceNet link.
@Read_DCBaudRate
Unsigned Integer
0 to 2
0 =125 Kbps, 1 = 255 Kbps, 2 = 500 Kbps
DF1 Tags
Tag Name
Data Type
Value Range
Description
@Read_DFX_ErrorDetectOption
Unsigned Integer
0 or 1
0 = BCC, 1 = CRC
@Read_DFX_HandshakeOption
Unsigned Integer
0 or 1
0 = Off, 1 = On
@Read_DFX_Parity
Unsigned Integer
0 to 2
0 = None, 1 = Even, 2 = Odd
@Read_DFX_PortMode
Unsigned Integer
0 – 3
0 = N-8-1, 1 = E-8-1, 2 = O-8-1, 3 = N-8-2
@Read_DFX_StopBits
Unsigned Integer
0, 2
0 = 1 Stop Bit, 2 = 2 Stop Bits
@Read_BaudRate
Unsigned Integer
2 to 6
2 = 1200, 3 = 2400, 4 = 4800,
5 = 9600, 6 = 19200
@Read_SerCommStatus
Unsigned Integer
0 to 2
0 = Connected, 1 = Offline, 2 = Hardware Failure
@Read_DFX_NodeAddress
Unsigned Integer
0 to 253
0 to 253