Rockwell Automation 2711-ND3 PanelBuilder v2.60 Software User Manual User Manual
Page 36

2–12
Installation
Publication 2711-6.0
For Pass-Through Select:
To Transfer Applications:
For These Terminals:
Remote I/O
between a computer on the DH+ link using a 1784-KTX communications card and
the Remote I/O port of a PanelView terminal on a Remote I/O network.
1784-KTX on DH+
RS-232 (DH-485)
between a computer on the DH+ link using a 1784-KTX communications card and
the RS-232 port of a PanelView terminal, connected to Port 0 of an SLC 5/04.
DH+
between a computer on the DH+ link using a 1784-KTX communications card and
the DH+ port of a PanelView terminal on the DH+ link.
Remote I/O
between a computer on the DH+ link using a 1784-PCMK communications card and
the Remote I/O port of a PanelView terminal on a Remote I/O network.
1784-PCMK on DH+
RS-232 (DH-485)
between a computer on the DH+ link using a 1784-PCMK communications card and
the RS-232 port of a PanelView terminal, connected to Port 0 of an SLC 5/04.
DH+
between a computer on the DH+ link using a 1784-PCMK communications card and
the DH+ port of a PanelView terminal on the DH+ link.
1784-PCMK on DH-485
DH-485
between a computer on the DH-485 network using a 1784-PCMK communications
card and the DH-485 port of a PanelView terminal.
2. Click the Add Device button.
A configuration dialog opens for the selected driver.
The following dialog opens for the DF1 (RS-232) on COM Port
driver.
Disables driver configuration
temporarily without removing
it from Configured Devices
list.
Default Driver Name
(can be edited)
DF1 parameters for a PanelView
terminal must be set to:
Baud: 19200
Parity: None
Error Detect: CRC
Unique number assigned
to INTERCHANGE driver
(This is not the computer’s COM port.)
COM Port Parameters should be set to:
COM Port 2 typically uses Interrupt (IRQ) 3
or
COM Port 1 typically uses Interrupt (IRQ) 4
If you change the COM Port setting, change the Interrupt to the
appropriate setting.