Creating Alarms
Publication 2711-6.0
Controller Acknowledges All Alarms for a Specific Trigger
The controller acknowledges all alarms activated by the same trigger.
The controller writes the Acknowledge All Value defined for the
trigger to the trigger’s Remote Ack address. The terminal notifies the
controller that it acknowledged all alarms for the trigger by writing
the Acknowledge All Value to the trigger’s Ack address.
Optional Fields are enabled and defined for the alarm triggers.
The PanelView reads the value 99 from the Remote
Ack address in the controller.
Alarm Configuration
– 6 alarms are assigned to the Extruder2 trigger, each with a different trigger value
– All alarm messages are configured to display and must be acknowledged
– A Remote Ack tag, Ack tag, and Acknowledge All Value are defined for each trigger
– 4 alarms are assigned to the Extruder1 trigger, each with a different trigger value
All alarms activated by the Extruder1 trigger are
acknowledged in the Alarm List.
The PanelView writes the Acknowledge All Value 99 to
the trigger’s Ack address (Ex1Ack).
The controller acknowledges all alarms activated by the
Extruder1 trigger by writing the trigger’s Acknowledge All
Value 99 to the Remote Ack address (Ex1RemoteAck) of
the trigger.
Alarm List
Extruder1
Msg B – Acknowledged
Extruder2
Msg B
Extruder2
Msg E
Extruder1
Msg A – Acknowledged
Extruder1
Msg D – Acknowledged
Extruder1
Msg B – Acknowledged
Extruder2
Msg A
➁
➂
➀
➃