23–14
Validating and Transferring Applications
Publication 2711-6.0
Remote I/O Pass-Through Setup
When you click the Setup button from the Download (or Upload)
Application dialog for a Remote I/O terminal, this dialog opens.
Note: If more than one COM port is configured with a DH+ driver,
the dialog will display available ports. Select the appropriate port.
To configure Remote I/O Pass-Through parameters:
1. Define Remote I/O Pass-Through parameters as described below.
2. Click OK to return to the Application Download dialog.
Use:
To:
Path
Single DH+ Network
Multiple DH+ Networks
Single DF1 Network
Transfer an application directly between a computer on the DH+ network and a
PanelView terminal through a single controller.
Transfer an application between a computer on the local DH+ network and a
PanelView terminal through a PLC controller on a remote DH+ network.
Transfer an application directly between a computer and a PanelView terminal
through the DF1 port on a PLC controller.
Local Bridge/PLC/SLC
Node Address
Link ID
Specify the address (0–77
octal)
of the PLC on the local DH+ network to which your
computer is connected (for Single DH+ Network). Specify address of Gateway
device on local network (for DH+ Multiple Networks).
Specify the unique ID number that identifies the local DH+ network to which your
computer is connected. This field is dimmed for a Single DH+ network.
Remote Bridge/PLC/SLC
Node Address
Link ID
Specify address (0–77
octal
) of the PLC on the remote DH+ network through which an
application is transferred. Dimmed if Single DH+ network selected.
Specify the unique ID number of the remote DH+ network through which an
application is transferred. Dimmed unless Multiple DH+ Networks is selected.
Operator Terminal
SLC Scanner Slot
Starting Module
Rack Address
Specify the number of the slot where the SLC scanner resides. The default is the
slot closest to the processor.
Specify the starting module group of the PanelView terminal in the Remote I/O rack.
Specify the address of the PanelView terminal on the Remote I/O network.