20–9
Terminal and Communication Setup
Publication 2711-6.0
This section shows how to define runtime parameters for a
PanelView terminal and PLC or SLC that will communicate on a
Remote I/O link.
The PanelView terminal operates as a single rack on the network.
You will define parameters for these two devices:
•
Remote I/O PanelView Terminal
•
PLC or SLC (with 1747-SN Scanner) Controller
PLC Controller
PanelView Terminal
RIO Port
Remote I/O Network
SLC Controller
with 1747-SN Scanner
or
The following table defines the PLC/Scanner types with options
supported by the Remote I/O PanelView terminal.
Controller/Scanner
Lowest
Rack #
Highest
Rack #
Pass-Through Support
Block Transfer Support
IBM PC 6008-SI
IBM PC 6008-SI
VME 6008-SV
EC
S 6008-S
0
7
No
Yes
V E 6008-SV
DEC QBUS 6008-SQ
0
7
No
Yes
PLC 5/11
3
3
All Series, All Revisions
Yes
PLC 5/15
1
3
Series B, Revision N or later
Yes
PLC 5/20
1
3
All Series, All Revisions
Yes
PLC 5/25
1
7
Series A, Revision J or later
Yes
PLC 5/30
1
7
Series A, Revision B or later
Yes
PLC 5/40
1
17
octal
Series A, Revision E or later
Series B, Revision B or later
Yes
PLC 5/60
PLC 5/80
1
27
octal
Series A, Revision E or later
Series B, Revision B or later
Yes
SLC 1747-SN Series A
0
3
No
No
SLC 1747-SN Series B
0
3
Yes
Yes
Other 1771-SN Subsystem
1
7
No
No
To configure Remote I/O communications:
1. Select the Setup tab from the Terminal Setup dialog.
2. Verify the terminal name entered in the Terminal Name field
The terminal name was defined when the application was created.
Defining Remote I/O
Communications
"