Creating Alarms
Publication 2711-6.0
Controller Acknowledges a Single Alarm for a Specific Trigger
The controller acknowledges a single alarm activated twice by the
same trigger. The controller writes the alarm’s trigger value to the
Remote Ack address defined for the trigger. The terminal notifies
the controller that it acknowledged the alarm by writing the alarm’s
trigger value to the Ack address.
Optional Fields are enabled and defined for the alarm triggers.
The PanelView reads the value 15 from the Remote
Ack address in the controller.
Alarm Configuration
– 4 alarms are assigned to the Extruder1 trigger, each with a different trigger value
– 6 alarms are assigned to the Extruder2 trigger, each with a different trigger value
– All alarms messages are configured to display and must be acknowledged
– A Remote Ack tag and Ack tag are defined for each trigger
Both occurrences of Msg B activated by the Extruder 1
trigger are acknowledged in the Alarm List.
The PanelView writes the trigger value 15 to the Ack
address (Ex1Ack) defined for the Extruder1 trigger.
The controller acknowledges Msg B activated by the
Extruder1 trigger by writing the alarm’s trigger value 15
to the Remote Ack address (Ex1RemoteAck) of the
trigger.
Alarm List
Extruder1
Msg B – Acknowledged
Extruder2
Msg B
Extruder2
Msg E
Extruder1
Msg A
Extruder1
Msg D
Extruder1
Msg B – Acknowledged
Extruder2
Msg A
➁
➂
➀
➃