beautypg.com

Function library, Function blocks, Setpoint input – Lenze EVS9332xK User Manual

Page 73: Actual value input and, Parameter control, Special features of ain1, The signal is read cyclically (1 ms), Special feature of ain2, The signal is read cyclically every 250 ms

background image

Function library

Function blocks

3.2.9

Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)

3−45

l

EDSVS9332K−EXT EN 4.0

3.2.9

Analog inputs via terminal X6/1, X6/2 and X6/3, X6/4 (AIN)

Purpose

These function blocks are the interface for analog signals as the

l

setpoint input,

l

actual value input and

l

parameter control.

C0034

1
2

AIN1

+
+

AIN1-OUT

AIN1-GAIN

AIN1-OFFSET

C0404/1

C0404/2

C0402

C0403

C0400

Fig. 3−20

Analog input via terminal X6/1, X6/2 (AIN1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AIN1−OFFSET

a

C0404/1

dec [%]

C0402

1

19502

AIN1−GAIN

a

C0404/2

dec [%]

C0403

1

19504

AIN1−OUT

a

C0400

Special features of AIN1

l

A dead band element can be integrated into the output signal at AIN1 via code C0034.
Together with the jumper position X2 (controller front) the function 4 ... 20 mA can be
implemented as a master current value.

l

The signal is read cyclically (1 ms).

3
4

AIN2

+
+

AIN2-OUT

AIN2-GAIN

AIN2-OFFSET

C0409/1

C0409/2

C0407

C0408

C0405

Fig. 3−21

Analog input via terminal X6/3, X6/4 (AIN2)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

AIN2−OFFSET

a

C0409/1

dec [%]

C0407

1

19503

AIN2−GAIN

a

C0409/2

dec [%]

C0408

1

19505

AIN2−OUT

a

C0405

Special feature of AIN2

l

The signal is read cyclically every 250

ms.

This manual is related to the following products: