Function library, Function blocks, 2 change phase/position through a defined path – Lenze EVS9332xK User Manual
Page 300: Wiring of the inputs, Master value at rfgph1−dfin

Function library
Function blocks
3.2.85
Ramp function generator for angle signals (RFGPH1)
3−272
l
EDSVS9332K−EXT EN 4.0
3.2.85.1
Change phase/position through a defined speed
Inputs for parameter setting:
l
FCODE C1476/1 = 5 m−units (position)
l
C1408/1 = 200.0 rpm: the drive travels to the target position with a master value speed of
200 rpm.
Control:
l
X5/E1 = HIGH: CDATA−XOFFS is traversed to 5 m−units at n = 200 rpm
l
X5/E1 = LOW: CDATA−XOFFS is traversed to 0 m−units at n = 200 rpm
l
The time required to reach the position results from the physical parameters selected.
t
t
RFGPH1−RFG−0
RFGPH1−IN
RFGPH1−OUT
C1408/1
C1408/1
C1408/1
3.2.85.2
Change phase/position through a defined path
RFGPH1
RFGPH1-IN
RFGPH1-RESET
RFGPH1-RFG-I=0
C1400/1
C1402/1
C1403/1
C1401/1
RFGPH1-T/DIST
C1400/2
C1401/3
RFGPH1-DFIN
C1404/1
C1405/1
CTRL
RFGPH1-DIST
C1402/2
C1403/2
RFGPH1-OUT
RFGPH1-IN-OLD
RFGPH1-RFG-0
C1400/3
C1401/2
CDATA-XOFFS
C1476/1
FCODE
FIXED0
DFIN-OUT
C1476/2
FCODE
9300kur026
Wiring of the inputs:
l
FCODE C1476/2 = 10 m−units (=RFGPH1−DIST)
l
FCODE C1476/1 = 2.5 m−units (=RFGPH1−IN)
l
Master value at RFGPH1−DFIN.