Function library

Function blocks

3.2.79

Position memory (PSAVE)

3−256

l

EDSVS9332K−EXT EN 4.0

3.2.79.2

Compare actual position with values stored

l

PSAVE−ON = HIGH:

– The inputs PSAVE−MPOS and PSAVE−ACTPOS are compared with the stored values. The

deviations are output at PSAVE−M−DIFF or PSAVE−ACT−DIFF.

PSAVEMDIFF

+ stored value * {PSAVEMPOS}

PSAVEACTDIFF

+ stored value * {PSAVEACTPOS}

– The evaluation of one of the channels can be suppressed by means of a code. In this case,

PSAVE−DIFF = 0

l

PSAVE−ON = LOW:

– The outputs PSAVE−DIFF = 0.

3.2.79.3

Output of status signals

The digital outputs are set according to the difference calculated (PSAVE−DIFF) if PSAVE−ON = HIGH.

l

A hysteresis can be set via code:

– for MPOS C1430/1 in m−units

– for ACTPOS C1430/2 in s−units

l

As long as −DIFF <

±C1430/x:

– −M−HI = LOW

– −M−LO = LOW

– ACT−HI = LOW

– ACT−LO = LOW

l

If −DIFF pos. and > +C1430/x

– −M−LO = HIGH and/or

– ACT−LO = HIGH

l

If −DIFF neg. and < −C1430/x

– −M−HI = HIGH and/or

– ACT−HI = HIGH

l

If one channel is suppressed through code C1431, the outputs of the corresponding channel
are set to LOW.