3.2.83

Homing function (REFC)

3−262

l

EDSVS9332K−EXT EN 4.0

3.2.83.1

Homing

There are different possibilities of homing the drive:

l

"Setting the reference once" is carried out for commissioning. For this, you enter the current
distance [s−units] of the tool to the machine zero point in C1367/1. This proecedure is
reasonable for machines with risk of collision).

– The function is carried out via the CCTRL or CCTRL2 function blocks. (

¶ 3−71 or 3−79)

l

A homing usually is carried out once after mains connection. By this, the home position of the
drive is found automatically. A homing is carried out via

– the REFC function block

– the CCTRL or CCTRL2 function blocks with the function "Set reference dynamically".

(

¶ 3−69 or 3−77)

Profile generator

The homing speed profile can be adapted to the application.

v

t

Referenzpunkt-Offset C0934

Nullimpuls

Referenzpunkt

C0935

C0936

C0936

REF-MARK

Fig. 3−213

Homing speed profile

Code

Meaning

Note

C0930

Encoder−gearbox factor numerator (motor speed)

Setting is required only if the actual value encoder is not
mounted to the motor

C0931

Encoder−gearbox factor denominator (encoder speed)

C0933

Selection of the edge of the touch probe signal at X5/E4

Regarding the homing modes with touch probe functionality,
the TP edge is the reference point for the home position offset

C0934

Homing point offset = number of increments after the zero
pulse

This reference applies: 65536 inc = 1 revolution. Selection up
to 2140000000 inc possible

C0935

Homing speed

Entry in [%] of n

max

(C0011)

C0936

Homing acceleration/deceleration time

Linear ramps

C0926/3

REFC−ACTPOS, current actual position

Read only

C0926/4

REFC−TARGET, current target position

Read only

The profile generator calculates the speed profile from the set profile parameters.

l

Parameter changes are possible during homing.

– C0935 and C0936 become effective if REFC−ON = LOW.

l

The drive should not be operated at the torque limit (MCTRL−MMAX = HIGH), otherwise the
drive cannot follow the speed profile.

– Increase acceleration / deceleration time C0936 until MCTRL−MMAX is no longer activated.

l

The phase controller in the MCTRL function block must be switched active.