Page 166

Function library
Function blocks
3.2.40
Drive control (DCTRL)
3−138
l
EDSVS9332K−EXT EN 4.0
Function
l
Quick stop (QSP)
l
Operation inhibited (DISABLE)
l
Controller inhibit (CINH)
l
TRIP set
l
TRIP reset
l
Change of parameter set (PAR)
l
Controller state
3.2.40.1
Quick stop (QSP)
The drive is braked to standstill via the deceleration ramp C105 and generates a holding torque.
l
The function can be controlled by three inputs
– Control word CAN−CTRL bit 3 of CAN−IN1
– Control word AIF−CTRL bit 3 of AIF−IN
– Control word C0135 bit 3
l
All inputs are linked by an OR−operation.
l
C0136/1 indicates the control word C0135
3.2.40.2
Operation inhibit (DISABLE)
In this state the drive cannot be started by the command: Controller enable. The power output stages
are inhibited. All controllers are reset.
l
The function can be controlled by three inputs
– Control word CAN−CTRL bit 8 of CAN−IN1
– Control word AIF−CTRL bit 8 of AIF−IN
– Control word C0135 bit 8
l
All inputs are linked by an OR−operation.
l
C0136/1 indicates the control word C0135