beautypg.com

46 freely assignable digital inputs (digin), Freely assignable digital inputs (digin), Function library – Lenze EVS9332xK User Manual

Page 189: Function blocks

background image

Function library

Function blocks

3.2.46

Freely assignable digital inputs (DIGIN)

3−161

l

EDSVS9332K−EXT EN 4.0

3.2.46

Freely assignable digital inputs (DIGIN)

Purpose

Reading and conditioning of the signals at the terminals X5/E1 to X5/E5.

E1
E2
E3
E4
E5

1

0

C0114/1...5

DIGIN

DIGIN1
DIGIN2
DIGIN3
DIGIN4
DIGIN5

C0443

28

DCTRL -X5/28

X5

DIGIN-CINH

1

Fig. 3−123

Freely assignable digital inputs (DIGIN)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

DIGIN−CINH

d

dec

Controller inhibit acts directly on the DCTRL
control

DIGIN1

d

C0443

dec

DIGIN2

d

C0443

dec

DIGIN3

d

C0443

dec

DIGIN4

d

C0443

dec

DIGIN5

d

C0443

dec

Function

The terminals X5/E1 to X5/E5 are scanned every millisecond. The level for every input can be
inverted. For this, proceed as follows:

l

Select code C0114 with corresponding subcode (e.g. subcode 3 for input X5/E3)

l

Enter the desired level as a parameter:

– 0 = Level not inverted (HIGH active)

– 1 = Level inverted (LOW active)

This manual is related to the following products: