Function library, Function blocks, Stop – Lenze EVS9332xK User Manual
Page 153

Function library
Function blocks
3.2.34
Conversion (CONVPHPHD2)
3−125
l
EDSVS9332K−EXT EN 4.0
(
STOP!
The function block can evaluate signal jumps at the input CONVPHPHD2−IN up to
max. 2147483647 inc (2
31
−1). At higher signal jumps the sign of the output signal
changes.
A position loss occurs which cannot be compensated anymore. You must carry out
a reset (CONVPHPHD2−RESET = HIGH).
0
1
-1
2 147 483 647 (2 -1)
31
-2 147 483 648 (-2 )
31
-2 147 483 647 (-2 +1)
31
1073741824 (2 /2)
31
-1073741824 (-2 /2)
31
Fig. 3−94
32−bit data representation in the cycle of numbers
Example 1
1. The input signal at CONVPHPHD2−IN is 65536 inc.
2. Now it jumps to −65536 inc.
3. The output CONVPHPHD2−OUT outputs, as expected, negative values
Example 2
1. The input signal at CONVPHPHD2−IN is 65536 inc.
2. Now it jumps to −2
31
−1 inc.
3. The output CONVPHPHD2−OUT, however, outputs positive values