Enter RIM Programming Mode

1. Hold down both SW1 and SW2 for about two seconds.
2. All seven LEDs on the RIM will flash three times.
3. Release both SW1 and SW2, and the unit is now in configuration mode.

Select Your Reader Type

The Keri MS (D4) and Wiegand (D5) types are currently supported.

1. Press SW1 to step through the supported reader types. Each press of SW1 will

step to the next reader type.

2. When the desired reader type LED is illuminated, press SW2. The reader type is

now set.

3. If you have selected Wiegand (D5) reader mode, the unit is now ready to configure

the RIM’s LED line control mode. Skip to section 3.3 for configuration instructions.

4. If you have selected Keri MS (D4) reader mode, press SW2 and the RIM is now

configured and the unit reboots to accept the new parameters.

5. All seven LEDs will flash three times as the unit reboots with the new configuration

parameters. When the LEDs stop flashing, the unit is operational.

NOTE: Do not remove power from the RIM during the reboot process. Loss of power dur-
ing rebooting will invalidate any configuration changes you have made.

Select Your Wiegand Reader LED Line Configuration

Perform this step if you are using a Wiegand reader.

1. Press SW1 to step through the supported LED line configuration types. Each press

of SW1 will step to the next LED line type.

2. When the desired LED line control mode LED is illuminated, press SW2. The LED

line control mode is now set. The RIM is now configured and the unit reboots to
accept the new parameters.

3. The RIM’s LEDs will be off for about 10 seconds as the unit resets itself. All seven

LEDs will flash as the unit is rebooting with the new configuration parameters.
When the LEDs stop flashing, the unit is operational.

NOTE: Do not remove power from the RIM during the reboot process. Loss of power dur-
ing rebooting will invalidate any
configuration changes you have made.

Verifying RIM Configuration

The corresponding reader type and line control mode LEDs are illuminated during oper-
ation. Refer to the Wiring Diagram and the table below to confirm your configuration set-
tings.