Specifying references for input data, continued – Schneider Electric Processor Adapter User Manual
Page 382

Configuring a Modbus Plus Network in Concept with Peer Cop
382
870 USE 101 10 V.2
Specifying References for Input Data, Continued
Procedure,
Continued
Continued on next page
Step
Action
2
Since you are addressing the device at address 2, you will use the line for Source
2. Type the value 300016
on that line in the Dest. Ref. column.
3
Type the value 1 in the Length column, indicating that the device at address 2 will
exchange one word of data. In this case, we will leave the default BIN setting.