beautypg.com

Accessing the remaining devices – Schneider Electric Processor Adapter User Manual

Page 276

background image

Using Peer Cop with Modsoft

276

870 USE 101 10 V.2

Accessing the Remaining Devices

Introduction

The I/O modules at Modbus Plus addresses 3 ... 5 can be configured individually in
a manner similar to that used for the 170 ADI 340 00 module at address 2.

Procedure

Follow the steps in the table below to access a new device address (in this case,
address 3), using the AddNode command.

Continued on next page

Step

Action

1

Push to move the cursor to the menu at the top of the Peer Cop screen.

2

Using a left or right arrow key as necessary, move the cursor onto the AddNode
command. Push .

Result: The Add Node popup appears over the Peer Cop screen with the cursor
flashing in the Link value field.

3

Make sure that the Link value in the Add Node popup is 1. Push .

Result: The Link value is set to 1, and the cursor moves to the Node value field of
the Add Node popup.