Overview of Momentum M1 Processor Adapters

36

870 USE 101 10 V.2

171 CCS 760 00, Continued

LED Indicators

This Processor Adapter has two LED indicators, RUN and COM ACT. Their
functions are described in the table below:

Specifications

The following table contains specifications for the 171 CCS 760 00 Momentum M1
Processor Adapter:

Continued on next page

LED

Status

Function

Start up

Both

Single flash. Indicates good health.

RUN

Green

On continuously when the CPU has received power and is
solving logic.

Flashes an error pattern if the CPU is in kernel mode.
(See

Run LED Flash Patterns and Error Codes on page 417)

Off

CPU is not powered up or is not solving logic.

COM ACT

Green

May be on continuously or blinking. Indicates activity on
Modbus port 1.

Off

No activity on Modbus port 1.

Memory

Internal Memory

256K bytes

User Memory

12K words

984LL Exec

160K words

IEC Exec

Flash RAM

256K bytes

Clock Speed

20 MHz

984LL Input and Output References

Registers

4096

Discretes

2048 (any combination of 0

x and 1x references) 984LL

IEC Input and Output References

Registers

4096

Discretes

2048 (any combination of 0

x and 1x references)