Saving to Flash in Modsoft

870 USE 101 10 V.2

305

Saving to Flash

Conditions for
Saving to Flash

In order to save the application program and state RAM values to Flash:

l

The Modsoft panel must be Online

l

The PLC must be stopped (not solving logic)

Save-to-Flash
Procedure

Follow the steps below to save to Flash.

Continued on next page

Step

Action

1

With the PLC online, go to the Ladder diagram editor or the Segment Status
Display.

2

From the PlcOps pull-down on the top menu, select Save to Flash.

Result: If the PLC is stopped when you select Save to Flash, the following screen
appears:

3

Answer the first two questions to specify the way you want the PLC to restart after a
power-down.