Changing the modbus address – Schneider Electric Processor Adapter User Manual

Page 342

background image

Configuring an M1 CPU with Concept

342

870 USE 101 10 V.2

Changing the Modbus Address

Overview

Each port can be assigned a Modbus network address in the range 1 ... 247. That
address must be unique with respect to all other device addresses on the same
Modbus networks.

Since Modbus port 1 and Modbus port 2 are always on different Modbus networks,
they can both be assigned the same address value without conflict. The factory-set
default for both ports is address 1.

Procedure

From the Modbus Port Settings dialog box, perform the steps in the following table
to change the Modbus Address:

Set the Stop Bit at 1.

Bridge mode is not supported.

Step

Address

1

Click on the Address field for the appropriate Modbus port.

2

Type a new value in the range 1 ... 247.