Other default settings in the peer cop dialog box – Schneider Electric Processor Adapter User Manual
Page 374
Configuring a Modbus Plus Network in Concept with Peer Cop
374
870 USE 101 10 V.2
Other Default Settings in the Peer Cop Dialog Box
Overview
This section describes the default settings for Health Timeout and Last Value.
Diagram
The first time you access the Peer Cop dialog box, the following screen appears:
Health Timeout
The default Timeout is
500 ms.
Timeout is the maximum interval that Modbus Plus on a Peer-Copped device will
remain healthy without communication activity. If this interval is exceeded, the
device will clear its network health bit and will no longer try to communicate via
Modbus Plus.
The timeout interval must be in the range 20...2000 ms, and it must be specified as
an increment of 20 ms.
Continued on next page