Issue 01/06 parameter description – Siemens 440 User Manual
Page 95
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
95
Note:
The DAC-linear characteristic is described by 4 coordinates, based on a two-point equation:
0777
P
0779
P
0778
P
0780
P
P0777
-
x
P0778
-
y
−
−
=
For calculations the point-gradient form (offset and gradient) is more advantageous:
0
y
x
m
y
+
⋅
=
The transformation between these two forms is given by:
0777
P
0779
P
0778
P
0780
P
m
−
−
=
%
200
0777
P
0779
P
0780
P
0777
P
0779
P
0778
P
y
0
≤
−
⋅
−
⋅
=
For scaling of the input the value of y_max and x_min has to be determined. This is done by the following
equations:
0778
P
0780
P
0779
P
0778
P
0777
P
0780
P
x
in
m
−
⋅
−
⋅
=
0777
P
0779
P
0778
P
0780
P
)
x
x
(
y
min
max
max
−
−
⋅
−
=
x
y
0
x
min
x
max
y
max
y
m
y
1
y
2
P0780
P0778
P0777
x
1
P0779
x
2
P0778[2]
Value y1 of DAC scaling
Min: 0
CStat:
CUT
Datatype: Float Unit:
-
Def:
0
P-Group: TERMINAL
Active: first confirm
QuickComm.: No
Max: 20
Defines y1 of output characteristic.
Index:
P0778[0] : Analog output 1 (DAC 1)
P0778[1] : Analog output 2 (DAC 2)
P0779[2]
Value x2 of DAC scaling
Min: -99999.0
CStat:
CUT
Datatype: Float Unit:
%
Def:
100.0
P-Group: TERMINAL
Active: first confirm
QuickComm.: No
Max: 99999.0
Defines x2 of output characteristic in [%].
Index:
P0779[0] : Analog output 1 (DAC 1)
P0779[1] : Analog output 2 (DAC 2)
Dependency:
Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to
be generated.
P0780[2]
Value y2 of DAC scaling
Min: 0
CStat:
CUT
Datatype: Float Unit:
-
Def:
20
P-Group: TERMINAL
Active: first confirm
QuickComm.: No
Max: 20
Defines y2 of output characteristic.
Index:
P0780[0] : Analog output 1 (DAC 1)
P0780[1] : Analog output 2 (DAC 2)
Level
2
Level
2
Level