Issue 01/06

Parameters

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

15

2.2

Quick commissioning (P0010 = 1)

The following parameters are necessary for quick commissioning (P0010 = 1).

Quick commissioning (P0010 = 1)

Par.-No. Name

Access

level

Cstat

P0100

Europe / North America

1

C

P0205 Inverter

application

3 C

P0300

Select motor type

2

C

P0304

Motor voltage rating

1

C

P0305

Motor current rating

1

C

P0307

Motor power rating

1

C

P0308

Motor cosPhi rating

1

C

P0309

Motor efficiency rating

1

C

P0310 Motor

frequency

rating

1 C

P0311 Motor

speed

rating

1 C

P0320

Motor magnetizing current

3

CT

P0335 Motor

cooling

2 CT

P0640

Motor overload factor [%]

2

CUT

P0700

Selection of command source

1

CT

P1000

Selection of frequency setpoint

1

CT

P1080 Min.

speed

1 CUT

P1082 Max.

speed

1 CT

P1120 Ramp-up

time

1 CUT

P1121 Ramp-down

time

1 CUT

P1135

OFF3 ramp-down time

2

CUT

P1300 Control

mode

2 CT

P1500

Selection of torque setpoint

2

CT

P1910

Select motor data identification

2

CT

P1960

Speed control optimisation

3

CT

P3900

End of quick commissioning

1

C

When P0010 = 1 is chosen, P0003 (user access level) can be used to select the
parameters to be accessed. This parameter also allows selection of a user-defined
parameter list for quick commissioning.
At the end of the quick commissioning sequence, set P3900 = 1 to carry out the
necessary motor calculations and clear all other parameters (not included in P0010
= 1) to their default settings.

Note
This applies only in Quick Commissioning mode.

Reset to Factory default

To reset all parameters to the factory default settings; the following parameters should
be set as follows:
Set P0010 = 30
Set P0970 = 1

Note
The reset process takes approximately 10 seconds to complete. Reset to Factory
default