2 quick commissioning (p0010 = 1), Reset to factory default – Siemens 440 User Manual
Page 15
Issue 01/06
Parameters
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
15
2.2
Quick commissioning (P0010 = 1)
The following parameters are necessary for quick commissioning (P0010 = 1).
Quick commissioning (P0010 = 1)
Par.-No. Name
Access
level
Cstat
P0100
Europe / North America
1
C
P0205 Inverter
application
3 C
P0300
Select motor type
2
C
P0304
Motor voltage rating
1
C
P0305
Motor current rating
1
C
P0307
Motor power rating
1
C
P0308
Motor cosPhi rating
1
C
P0309
Motor efficiency rating
1
C
P0310 Motor
frequency
rating
1 C
P0311 Motor
speed
rating
1 C
P0320
Motor magnetizing current
3
CT
P0335 Motor
cooling
2 CT
P0640
Motor overload factor [%]
2
CUT
P0700
Selection of command source
1
CT
P1000
Selection of frequency setpoint
1
CT
P1080 Min.
speed
1 CUT
P1082 Max.
speed
1 CT
P1120 Ramp-up
time
1 CUT
P1121 Ramp-down
time
1 CUT
P1135
OFF3 ramp-down time
2
CUT
P1300 Control
mode
2 CT
P1500
Selection of torque setpoint
2
CT
P1910
Select motor data identification
2
CT
P1960
Speed control optimisation
3
CT
P3900
End of quick commissioning
1
C
When P0010 = 1 is chosen, P0003 (user access level) can be used to select the
parameters to be accessed. This parameter also allows selection of a user-defined
parameter list for quick commissioning.
At the end of the quick commissioning sequence, set P3900 = 1 to carry out the
necessary motor calculations and clear all other parameters (not included in P0010
= 1) to their default settings.
Note
This applies only in Quick Commissioning mode.
Reset to Factory default
To reset all parameters to the factory default settings; the following parameters should
be set as follows:
Set P0010 = 30
Set P0970 = 1
Note
The reset process takes approximately 10 seconds to complete. Reset to Factory
default