beautypg.com

Parameter description issue 01/06 – Siemens 440 User Manual

Page 212

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

212

6SE6400-5BB00-0BP0

P2159[3]

Threshold frequency f_3

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

30.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 650.00

Threshold_3 for comparing frequency to thresholds.

Tconst. speed filt

0 ... 1000 [ms]

P2153.D (5)

Threshold freq f_3

0.00 ... 650.00 [Hz]

P2159.D ( 30.00)

Hyst . freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

Delay time of f _3

0 ... 10000 [ms]

P2160.D (10)

Delay time of f _3

0 ... 10000 [ms]

P2160.D (10)

| f_act | <= f_3

| f_act | > f_3

T 0

T 0

f_act

r2198 Bit03

r2198 Bit02

| f_act | <= f_3

Threshold freq f_3

0.00 ... 650.00 [Hz]

P2159.D (30.00)

Hyst. freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

0

1

{

0

1

{

| f_act | > f_3

r2169

Index:

P2159[0] : 1st. Drive data set (DDS)
P2159[1] : 2nd. Drive data set (DDS)
P2159[2] : 3rd. Drive data set (DDS)

P2160[3]

Delay time of threshold freq f_3

Min: 0

CStat:

CUT

Datatype: U16 Unit:

ms

Def:

10

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10000

Delay time for comparing frequency to threshold f_3 (P2159).

Index:

P2160[0] : 1st. Drive data set (DDS)
P2160[1] : 2nd. Drive data set (DDS)
P2160[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2159 (threshold frequency f_3)

P2161[3]

Min. threshold for freq. setp.

Min: 0.00

CStat:

CUT

Datatype: Float Unit:

Hz

Def:

3.00

P-Group: ALARMS

Active: Immediately

QuickComm.: No

Max: 10.00

Minimum threshold value for comparing frequency setpoint.

0

1

{

0

1

{

0

Setp.min.threshold

0.00 ... 10.00 [Hz]

P2161.D (3.00)

Hyst . freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

Hyst . freq. f_hys

0.00 ... 10.00 [Hz]

P2150.D (3.00)

| f_set | <= P2161

| f_set | <= P2161

f_set > 0

f_set > 0

f_set

r2198 Bit04

r2198 Bit05

Index:

P2161[0] : 1st. Drive data set (DDS)
P2161[1] : 2nd. Drive data set (DDS)
P2161[2] : 3rd. Drive data set (DDS)

Level

2

Level

2

Level

2