F0054 incorrect i/o module stop ii, F0060 asic time slice overflow stop ii, F0070 cb setpoint fault stop ii – Siemens 440 User Manual
Page 312: F0071 uss(bop link) setpoint fault stop ii, F0072 uss(comm link) setpoint fault stop ii, F0080 adc input signal lost stop ii, F0085 external fault stop ii

Faults and Alarms
Issue 01/06
MICROMASTER 440 Parameter List
312
6SE6400-5BB00-0BP0
F0054 Incorrect I/O module
STOP II
Quit
Refer to F0001
Cause
-
incorrect I/O module inserted.
-
no ID of the I/O module found, no data.
Diagnosis & Remedy
Please check the following:
-
check I/O data, if required repeat the operation
-
the installation of the I/O module in the inverter if required, replace the I/O module
F0060 Asic time slice overflow
STOP II
Quit
Refer to F0001
Cause
-
internal communications failure/error
Diagnosis & Remedy
-
if the error still occurs, replace the inverter.
-
contact customer service!
F0070 CB setpoint fault
STOP II
Quit
Refer to F0001
Cause
-
no setpoints received via the communications bus during the telegram failure time.
Diagnosis & Remedy
-
check the communications module (CB) and communications partner.
F0071 USS(BOP link) setpoint fault
STOP II
Quit
Refer to F0001
Cause
-
no setpoint was received via the USS during the telegram off time
Diagnosis & Remedy
-
check USS master
F0072 USS(COMM link) setpoint fault
STOP II
Quit
Refer to F0001
Cause
-
no setpoints received via the USS during the telegram off time
Diagnosis & Remedy
-
check USS master
F0080 ADC input signal lost
STOP II
Quit
Refer to F0001
Cause
- wire
breakage
-
signal outside the limit values
F0085 External fault
STOP II
Quit
Refer to F0001
Cause
-
external fault as a result of command input via terminals.
Diagnosis & Remedy
-
inhibit terminal input to initiate fault.