beautypg.com

Siemens 440 User Manual

Page 126

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

126

6SE6400-5BB00-0BP0

P1076[3]

CI: Additional setpoint scaling

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

1:0

P-Group: SETPOINT

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines source of scaling for additional setpoint (to be added to main setpoint).

Index:

P1076[0] : 1st. Command data set (CDS)
P1076[1] : 2nd. Command data set (CDS)
P1076[2] : 3rd. Command data set (CDS)

Common Settings:

1 = Scaling of 1.0 (100%)
755 = Analog input 1 Setpoint
1024 = Fixed Frequency Setpoint
1050 = MOP Setpoint

r1078

CO: Total frequency setpoint

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: SETPOINT

Max: -

Displays sum of main and additional setpoints in [Hz].

r1079

CO: Selected frequency setpoint

Min: -

Datatype: Float Unit:

Hz

Def:

-

P-Group: SETPOINT

Max: -

Displays selected frequency setpoint.

Following frequency setpoints are displayed:
-

r1078 Total frequency setpoint

-

P1058 JOG frequency right

-

P1059 JOG frequency left

Dependency:

P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.

Note:

P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.

Level

3

Level

3

Level

3