16 setpoint source – Siemens 440 User Manual

Page 110

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

110

6SE6400-5BB00-0BP0

3.16 Setpoint

source

P1000[3]

Selection of frequency setpoint

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

2

P-Group: SETPOINT

Active: first confirm

QuickComm.: Yes Max: 77

Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from
the least significant digit (i.e., 0 to 7) and any additional setpoint from the most significant digit (i.e., x0
through to x7).

Possible Settings:

0

No main setpoint

1 MOP

setpoint

2 Analog

setpoint

3 Fixed

frequency

4

USS on BOP link

5

USS on COM link

6

CB on COM link

7

Analog setpoint 2

10 No main setpoint + MOP setpoint
11 MOP setpoint

+ MOP setpoint

12 Analog setpoint

+ MOP setpoint

13 Fixed frequency + MOP setpoint
14 USS on BOP link + MOP setpoint
15 USS on COM link + MOP setpoint
16 CB on COM link + MOP setpoint
17 Analog setpoint 2 + MOP setpoint
20 No main setpoint + Analog setpoint
21 MOP setpoint

+ Analog setpoint

22 Analog setpoint

+ Analog setpoint

23 Fixed frequency + Analog setpoint
24 USS on BOP link + Analog setpoint
25 USS on COM link + Analog setpoint
26 CB on COM link + Analog setpoint
27 Analog setpoint 2 + Analog setpoint
30 No main setpoint + Fixed frequency
31 MOP setpoint

+ Fixed frequency

32 Analog setpoint

+ Fixed frequency

33 Fixed frequency + Fixed frequency
34 USS on BOP link + Fixed frequency
35 USS on COM link + Fixed frequency
36 CB on COM link + Fixed frequency
37 Analog setpoint 2 + Fixed frequency
40 No main setpoint + USS on BOP link
41 MOP setpoint

+ USS on BOP link

42 Analog setpoint

+ USS on BOP link

43 Fixed frequency + USS on BOP link
44 USS on BOP link + USS on BOP link
45 USS on COM link + USS on BOP link
46 CB on COM link + USS on BOP link
47 Analog setpoint 2 + USS on BOP link
50 No main setpoint + USS on COM link
51 MOP setpoint

+ USS on COM link

52 Analog setpoint

+ USS on COM link

53 Fixed frequency + USS on COM link
54 USS on BOP link + USS on COM link
55 USS on COM link + USS on COM link
57 Analog setpoint 2 + USS on COM link
60 No main setpoint + CB on COM link
61 MOP setpoint

+ CB on COM link

62 Analog setpoint

+ CB on COM link

63 Fixed frequency + CB on COM link
64 USS on BOP link + CB on COM link
66 CB on COM link + CB on COM link
67 Analog setpoint 2 + CB on COM link
70 No main setpoint + Analog setpoint 2
71 MOP setpoint

+ Analog setpoint 2

72 Analog setpoint

+ Analog setpoint 2

73 Fixed frequency + Analog setpoint 2
74 USS on BOP link + Analog setpoint 2
75 USS on COM link + Analog setpoint 2
76 CB on COM link + Analog setpoint 2
77 Analog setpoint 2 + Analog setpoint 2

Level

1