P0724
Debounce time for digital inputs
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
3
P-Group: COMMANDS
Active: Immediately
QuickComm.: No
Max: 3
Defines debounce time (filtering time) used for digital inputs.
Possible Settings:
0
No debounce time
1
2.5 ms debounce time
2
8.2 ms debounce time
3
12.3 ms debounce time
P0725
PNP / NPN digital inputs
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
1
P-Group: COMMANDS
Active: Immediately
QuickComm.: No
Max: 1
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously.
The following is valid by using the internal supply:
Possible Settings:
0
NPN mode ==> low active
1
PNP mode ==> high active
Value:
NPN: Terminals 5/6/7/8/16/17 must be connected via terminal 28 ( O V).
PNP: Terminals 5/6/7/8/16/17 must be connected via terminal 9 (24 V).
Level