Parameter description issue 01/06, P3980 commissioning command selection, P3981 reset active fault – Siemens 440 User Manual
Page 258
Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
258
6SE6400-5BB00-0BP0
P3980
Commissioning command selection
Min: 0
CStat:
T
Datatype: U16 Unit:
-
Def:
0
P-Group: -
Active: first confirm
QuickComm.: No
Max: 67
Toggles command and setpoint sources between freely programmable BICO parameters and fixed
command/setpoint profiles for commissioning.
The command and setpoint sources can be changed independently. The tens digit selects the command
source, the ones digit the setpoint source.
Possible Settings:
0
Cmd = BICO parameter
Setpoint = BICO parameter
1
Cmd = BICO parameter
Setpoint = MOP setpoint
2
Cmd = BICO parameter
Setpoint = Analog setpoint
3
Cmd = BICO parameter
Setpoint = Fixed frequency
4
Cmd = BICO parameter
Setpoint = USS on BOP link
5
Cmd = BICO parameter
Setpoint = USS on COM link
6
Cmd = BICO parameter
Setpoint = CB on COM link
7
Cmd = BICO parameter
Setpoint = Analog 2 setp
10 Cmd = BOP
Setpoint = BICO parameter
11 Cmd = BOP
Setpoint = MOP setpoint
12 Cmd = BOP
Setpoint = Analog setpoint
13 Cmd = BOP
Setpoint = Fixed frequency
15 Cmd = BOP
Setpoint = USS on COM link
16 Cmd = BOP
Setpoint = CB on COM link
17 Cmd = BOP
Setpoint = Analog 2 setp
40 Cmd = USS on BOP link
Setpoint = BICO parameter
41 Cmd = USS on BOP link
Setpoint = MOP setpoint
42 Cmd = USS on BOP link
Setpoint = Analog setpoint
43 Cmd = USS on BOP link
Setpoint = Fixed frequency
44 Cmd = USS on BOP link
Setpoint = USS on BOP link
45 Cmd = USS on BOP link
Setpoint = USS on COM link
46 Cmd = USS on BOP link
Setpoint = CB on COM link
47 Cmd = USS on BOP link
Setpoint = Analog 2 setp
50 Cmd = USS on COM link
Setpoint = BICO parameter
51 Cmd = USS on COM link
Setpoint = MOP setpoint
52 Cmd = USS on COM link
Setpoint = Analog setpoint
53 Cmd = USS on COM link
Setpoint = Fixed frequency
54 Cmd = USS on COM link
Setpoint = USS on BOP link
55 Cmd = USS on COM link
Setpoint = USS on COM link
57 Cmd = USS on COM link
Setpoint = Analog 2 setp
60 Cmd = CB on COM link
Setpoint = BICO parameter
61 Cmd = CB on COM link
Setpoint = MOP setpoint
62 Cmd = CB on COM link
Setpoint = Analog setpoint
63 Cmd = CB on COM link
Setpoint = Fixed frequency
64 Cmd = CB on COM link
Setpoint = USS on BOP link
66 Cmd = CB on COM link
Setpoint = CB on COM link
67 Cmd = CB on COM link
Setpoint = Analog 2 setp
P3981 Reset
active
fault
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: ALARMS
Active: first confirm
QuickComm.: No
Max: 1
Resets active faults when changed from 0 to 1.
Possible Settings:
0
No fault reset
1 Reset
fault
Note:
Automatically reset to 0.
Details:
See r0947 (last fault code)
r3986[2]
Number of parameters
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: -
Max: -
Number of parameters on the drive
Index:
r3986[0] : Read only
r3986[1] : Read & write
Level
4
Level
4
Level
4