F0003 undervoltage stop ii, F0004 inverter overtemperature stop ii, F0011 motor overtemperature stop ii – Siemens 440 User Manual
Page 308: F0012 no inverter temperature signal stop i
Faults and Alarms
Issue 01/06
MICROMASTER 440 Parameter List
308
6SE6400-5BB00-0BP0
F0003 Undervoltage
STOP
II
Quit
Refer to F0001
Cause
-
line voltage failed
-
shock stressing outside the permissible limits.
Diagnosis & Remedy
Please check the following:
-
is the line supply voltage within the permissible range?
-
is the line supply voltage stable with respect to sporadic failures and voltage dips (brown-outs) ?
F0004 Inverter overtemperature
STOP II
Quit
Refer to F0001
Cause
- inadequate
cooling
-
ambient temperature is too high.
ambient temperature is too high.
Diagnosis & Remedy
Please check the following:
-
is the pulse frequency P1800 set to the factory setting ? If required reset P1800.
-
does the ambient temperature lie within the permissible limits ?
-
reduce the load and / or ensure adequate cooling
Please check the following:
-
does the fan rotate if the inverter is operational ?
F0005 Inverter I2T
STOP II
Quit
Refer to F0001
Cause
- inverter
overloaded.
-
load duty cycle too high.
-
the motor power rating (P0307) is greater than that of the inverter (r0206).
-
100 % overload reached (refer to utilization r0036)
Diagnosis & Remedy
Please check the following:
-
does the load duty cycle lie within the permissible limits?
-
use a motor with a lower rating (motor power P0307 is greater than ls inverter power r0206)
F0011 Motor overtemperature
STOP II
Quit
Refer to F0001
Cause
Motor overloaded
Diagnosis & Remedy
Please check the following:
-
is the load cycle correct ?
-
are the rated/nominal motor overtemperatures correct (P0626-P0628) ?
-
is the alarm threshold correct for the motor temperature (P0604) ?
F0012 No inverter temperature signal
STOP I
Quit
Refer to F0001
Cause
-
wire breakage of the inverter-temperature sensor (heatsink)
Diagnosis & Remedy
-
replace the inverter