Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
79
P0704[3]
Function of digital input 4
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
15
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 99
Selects function of digital input 4.
Possible Settings:
0
Digital input disabled
1 ON/OFF1
2
ON reverse /OFF1
3
OFF2 - coast to standstill
4
OFF3 - quick ramp-down
9 Fault
acknowledge
10 JOG
right
11 JOG
left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
25 DC brake enable
29 External
trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Index:
P0704[0] : 1st. Command data set (CDS)
P0704[1] : 2nd. Command data set (CDS)
P0704[2] : 3rd. Command data set (CDS)
Details:
See P0701 (function of digital input 1).
P0705[3]
Function of digital input 5
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
15
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 99
Selects function of digital input 5.
Possible Settings:
0
Digital input disabled
1 ON/OFF1
2
ON reverse /OFF1
3
OFF2 - coast to standstill
4
OFF3 - quick ramp-down
9 Fault
acknowledge
10 JOG
right
11 JOG
left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
25 DC brake enable
29 External
trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Index:
P0705[0] : 1st. Command data set (CDS)
P0705[1] : 2nd. Command data set (CDS)
P0705[2] : 3rd. Command data set (CDS)
Details:
See P0701 (function of digital input 1).
Level
2
Level
2