Siemens 440 User Manual
Page 228

Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
228
6SE6400-5BB00-0BP0
P2222[3]
BI: Fixed PID setp. select Bit 2
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 2
Index:
P2222[0] : 1st. Command data set (CDS)
P2222[1] : 2nd. Command data set (CDS)
P2222[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
P2223[3]
BI: Fixed PID setp. select Bit 3
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
722:3
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 3
Index:
P2223[0] : 1st. Command data set (CDS)
P2223[1] : 2nd. Command data set (CDS)
P2223[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
r2224
CO: Act. fixed PID setpoint
Min: -
Datatype: Float Unit:
%
Def:
-
P-Group: TECH
Max: -
Displays total output of PID fixed setpoint selection.
Note:
r2224 = 100 % corresponds to 4000 hex
P2225[3]
Fixed PID setpoint mode - Bit 4
Min: 1
CStat:
CT
Datatype: U16 Unit:
-
Def:
1
P-Group: TECH
Active: first confirm
QuickComm.: No
Max: 2
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Possible Settings:
1 Direct
selection
2
Direct selection + ON command
Index:
P2225[0] : 1st. Command data set (CDS)
P2225[1] : 2nd. Command data set (CDS)
P2225[2] : 3rd. Command data set (CDS)
P2226[3]
BI: Fixed PID setp. select Bit 4
Min: 0:0
CStat:
CT
Datatype: U32 Unit:
-
Def:
722:4
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 4
Index:
P2226[0] : 1st. Command data set (CDS)
P2226[1] : 2nd. Command data set (CDS)
P2226[2] : 3rd. Command data set (CDS)
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
Level
3
Level
3
Level
2
Level
3
Level
3