beautypg.com

3 speed controller pre-control – Siemens 440 User Manual

Page 172

background image

Parameter Description

Issue 01/06

MICROMASTER 440 Parameter List

172

6SE6400-5BB00-0BP0

3.29.2.3 Speed controller pre-control

P1496[3]

Scaling accel. precontrol

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

0.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 400.0

Enters scaling of acceleration in [%].

The response of setpoint changes for the speed control loop can be improved using the precontrol function
(P1496). Precontrol is derived from the differential frequency setpoint multiplied by the mass inertia P0341;
P0342 is then supplied as a torque setpoint to the current controller. If the filter (VC: P1442, SLVC: P1452)
is applied in the correct manner, the derived speed controller is only required to control a small deviation in
the value of the corrected variable. Setpoint changes are then passed by the speed controller and are
quickly executed.

Torque

setpoint

Freq. setpoint

PI

Speed

controller

r1538

r1539

r1538

r1539

r1538

r1539

P1496

P0341 P0342

P1492 P1489 P1488

Droop

r1490

150 ms

r1518

Act. frequency

=0

>0

r0063

r1170

r0079

r1508

Index:

P1496[0] : 1st. Drive data set (DDS)
P1496[1] : 2nd. Drive data set (DDS)
P1496[2] : 3rd. Drive data set (DDS)

Note:

P1496 = 0:
Precontrol disabled

P1496 > 0:
Precontrol enabled

P1496 = 100:
Standard setting for precontrol

P1499[3]

Scaling accel. torque control

Min: 0.0

CStat:

CUT

Datatype: Float Unit:

%

Def:

100.0

P-Group: CONTROL

Active: Immediately

QuickComm.: No

Max: 400.0

Enters scaling of acceleration in [%] for sensorless torque control (SLVC) at low frequencies.

Index:

P1499[0] : 1st. Drive data set (DDS)
P1499[1] : 2nd. Drive data set (DDS)
P1499[2] : 3rd. Drive data set (DDS)

Level

3

Level

3