220
6SE6400-5BB00-0BP0
P2184[3]
Belt threshold frequency 3
Min: 0.00
CStat:
CUT
Datatype: Float Unit:
Hz
Def:
50.00
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 650.00
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Index:
P2184[0] : 1st. Drive data set (DDS)
P2184[1] : 2nd. Drive data set (DDS)
P2184[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2185[3]
Upper torque threshold 1
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
99999.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 99999.0
Upper limit threshold value 1 for comparing actual torque.
Index:
P2185[0] : 1st. Drive data set (DDS)
P2185[1] : 2nd. Drive data set (DDS)
P2185[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2186[3]
Lower torque threshold 1
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
0.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 99999.0
Lower limit threshold value 1 for comparing actual torque.
Index:
P2186[0] : 1st. Drive data set (DDS)
P2186[1] : 2nd. Drive data set (DDS)
P2186[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2187[3]
Upper torque threshold 2
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
99999.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 99999.0
Upper limit threshold value 2 for comparing actual torque.
Index:
P2187[0] : 1st. Drive data set (DDS)
P2187[1] : 2nd. Drive data set (DDS)
P2187[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2188[3]
Lower torque threshold 2
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
0.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 99999.0
Lower limit threshold value 2 for comparing actual torque.
Index:
P2188[0] : 1st. Drive data set (DDS)
P2188[1] : 2nd. Drive data set (DDS)
P2188[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
P2189[3]
Upper torque threshold 3
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
99999.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 99999.0
Upper limit threshold value 3 for comparing actual torque.
Index:
P2189[0] : 1st. Drive data set (DDS)
P2189[1] : 2nd. Drive data set (DDS)
P2189[2] : 3rd. Drive data set (DDS)
Details:
See P2182 (belt threshold frequency 1).
Level
2
Level
2
Level
2
Level
2
Level
2
Level
2