beautypg.com

Siemens 440 User Manual

Page 111

background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

111

Index:

P1000[0] : 1st. Command data set (CDS)
P1000[1] : 2nd. Command data set (CDS)
P1000[2] : 3rd. Command data set (CDS)

Example:

Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the
motor potentiometer.

P1000 =

1

2

⇒ P1070 = 755

P1070 CI: Main setpoint

r0755 CO: Act. ADC after scal. [4000h]

P1000 = 1

2

⇒ P1075 = 1050

P1075 CI: Additional setpoint

r1050 CO: Act. Output freq. of the MOP

Example P1000 = 12 :

MOP

ADC

FF

USS

BOP link

USS

COM link

CB

COM link

ADC2

P1000 =

1

2

P1000 = 1

2

Sequence control

Main

setpoint

Setpoint

channel

Motor

control

Additonal

setpoint

Caution:

Be aware, by changing of parameter P1000 all BICO parameters (see table below) are modified.

Note:

Single digits denote main setpoints that have no additional setpoint.

Changing this parameter sets (to default) all settings on item selected (see table).