6 torque / power limiting – Siemens 440 User Manual
Page 177
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
177
3.29.2.6 Torque / power limiting
P1521[3]
CO: Lower torque limit
Min: -99999.00
CStat:
CUT
Datatype: Float Unit:
Nm
Def:
-5.13
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 99999.00
Enters fixed value of lower torque limitation.
P1521
max
P1521
def
r0333
1.5
⋅
−
=
r0333
4
⋅
±
=
Index:
P1521[0] : 1st. Drive data set (DDS)
P1521[1] : 2nd. Drive data set (DDS)
P1521[2] : 3rd. Drive data set (DDS)
P1522[3]
CI: Upper torque limit
Min: 0:0
CStat:
T
Datatype: U32 Unit:
-
Def:
1520:0
P-Group: CONTROL
Active: first confirm
QuickComm.: No
Max: 4000:0
Selects source of upper torque limitation.
Index:
P1522[0] : 1st. Command data set (CDS)
P1522[1] : 2nd. Command data set (CDS)
P1522[2] : 3rd. Command data set (CDS)
P1523[3]
CI: Lower torque limit
Min: 0:0
CStat:
T
Datatype: U32 Unit:
-
Def:
1521:0
P-Group: CONTROL
Active: first confirm
QuickComm.: No
Max: 4000:0
Selects source of lower torque limitation.
Index:
P1523[0] : 1st. Command data set (CDS)
P1523[1] : 2nd. Command data set (CDS)
P1523[2] : 3rd. Command data set (CDS)
P1525[3]
Scaling lower torque limit
Min: -400.0
CStat:
CUT
Datatype: Float Unit:
%
Def:
100.0
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 400.0
Enters scaling of lower torque limitation in [%].
Index:
P1525[0] : 1st. Drive data set (DDS)
P1525[1] : 2nd. Drive data set (DDS)
P1525[2] : 3rd. Drive data set (DDS)
Note:
P1525 = 100 % = standard setting
r1526
CO: Upper torque limitation
Min: -
Datatype: Float Unit:
Nm
Def:
-
P-Group: CONTROL
Max: -
Displays actual upper torque limitation.
f
1
~
Torque limitation
Resultant
torque limit
Power
limitation
|f
act
r1526
r1527
Stall
limitation
P1530
P1531
f
1
~
2
Constant
torque
f
stall
Constant
power
|
|M
|
Stall
power
Dependency:
The parameters r1526 and r1527 depend on P1520, P1521, P1522, P1523 and P1525.
Level
2
Level
3
Level
3
Level
3
Level
3