31 motor data identification – Siemens 440 User Manual
Page 189

Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
189
P1825
On-state voltage of IGBT
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
V
Def:
1.4
P-Group: INVERTER
Active: Immediately
QuickComm.: No
Max: 20.0
Corrects on-state voltage of the IGBTs.
P1828
Gating unit dead time
Min: 0.00
CStat:
CUT
Datatype: Float Unit:
us
Def:
0.50
P-Group: INVERTER
Active: first confirm
QuickComm.: No
Max: 3.50
Sets compensation time of gating unit interlock.
3.31
Motor data identification
P1909[3]
Ctrl. word of motor data ident.
Min: 0
CStat:
CUT
Datatype: U16 Unit:
-
Def:
1
P-Group: CONTROL
Active: first confirm
QuickComm.: No
Max: 1
Control word of motor data identification.
Bitfields:
Bit00 Estimation of Xs 0 NO 1 YES
Index:
P1909[0] : 1st. Drive data set (DDS)
P1909[1] : 2nd. Drive data set (DDS)
P1909[2] : 3rd. Drive data set (DDS)
P1910
Select motor data identification
Min: 0
CStat:
CT
Datatype: U16 Unit:
-
Def:
0
P-Group: MOTOR
Active: first confirm
QuickComm.: Yes Max: 20
Performs a motor data identification.
Possible Settings:
0 Disabled
1
Identification of all parameters with parameter change
2
Identification of all parameters without parameter change
3
Identification of saturation curve with parameter change
4
Identification of saturation curve without parameter change
5
Identification of XsigDyn (r1920) without parameter change
6
Identification of Tdead (r1926) without parameter change
7
Identification of Rs (r1912 ) without parameter change
8
Identification of Xs (r1915) without parameter change
9
Identification of Tr (r1913) without parameter change
10 Identification of Xsigma (r1914) without parameter change
20 Set voltage vector
Common Settings:
P1910 = 1:
All motor data and inverter characteristic will be identified and parameter will be changed.
-
P0350 stator resistance,
-
P0354 rotor resistance,
-
P0356 stator leakage inductance,
-
P0358 rotor leakage inductance,
-
P0360 main inductance
-
P1825 on-state voltage of IGBTs
-
P1828 compensation time of gating unit interlock
P1910 = 3:
Saturation curve will be identified and parameter will be changed.
-
P0362 ... P0365 magnetizing curve flux 1 .. 4
-
P0366 ... P0369 magnetizing curve imag 1 .. 4
Caution:
Motor identification should normally be performed on a cold motor. However, the identification of the motor
data should only be performed if the motor temperature is within 5°C of the measured ambient temperature
stored in P0625. If the motor identification is not within the 5ºC limit then the correct functioning of Vector
Control (VC, SLVC) cannot be guaranteed. This may cause instabilities when using vector control.
The motor rating plate information with respect to the connection of the motor windings (Star or delta
connection) must be correct in order to establish the correct equivalent circuit data. The motor identification
calculates this data based on a Phase of a Star equivalent circuit P0350 - P0360, irrespective of whether
the motor is connected star or delta. This must be considered when the motor data is input directly.
Note:
-
In order to that the motor identification routine supplies the correct data, before selecting, fast
commissioning should be carried-out.
-
If the motor data identification routine is activated (e.g. P1910 = 1), then at the next ON command, the
measuring operation is started and alarm A0541 is generated. After the measurement is completed,
both P1910 and the alarm are reset.
Level
4
Level
4
Level
4
Level
2