Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
224
6SE6400-5BB00-0BP0
Direct selection of PID-FF1 P2201 via DIN 1:
P2216
P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
r2224
r0722.0
P2220
1
2,3
P2201
0
. . . .
0
. . .
.
. . . .
Dependency:
P2200 = 1 required in user access level 2 to enable setpoint source.
Note:
You may mix different types of frequencies; however, remember that they will be summed if selected
together.
P2201 = 100 % corresponds to 4000 hex
P2202[3]
Fixed PID setpoint 2
Min: -200.00
CStat:
CUT
Datatype: Float Unit:
%
Def:
10.00
P-Group: TECH
Active: Immediately
QuickComm.: No
Max: 200.00
Defines Fixed PID Setpoint 2
Index:
P2202[0] : 1st. Drive data set (DDS)
P2202[1] : 2nd. Drive data set (DDS)
P2202[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2203[3]
Fixed PID setpoint 3
Min: -200.00
CStat:
CUT
Datatype: Float Unit:
%
Def:
20.00
P-Group: TECH
Active: Immediately
QuickComm.: No
Max: 200.00
Defines Fixed PID Setpoint 3
Index:
P2203[0] : 1st. Drive data set (DDS)
P2203[1] : 2nd. Drive data set (DDS)
P2203[2] : 3rd. Drive data set (DDS)
Details:
See P2201 fixed PID setpoint 1 (FF-PID 1).
P2204[3]
Fixed PID setpoint 4
Min: -200.00
CStat:
CUT
Datatype: Float Unit:
%
Def:
30.00
P-Group: TECH
Active: Immediately
QuickComm.: No
Max: 200.00
Defines Fixed PID Setpoint 4
Index:
P2204[0] : 1st. Drive data set (DDS)
P2204[1] : 2nd. Drive data set (DDS)
P2204[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
P2205[3]
Fixed PID setpoint 5
Min: -200.00
CStat:
CUT
Datatype: Float Unit:
%
Def:
40.00
P-Group: TECH
Active: Immediately
QuickComm.: No
Max: 200.00
Defines Fixed PID Setpoint 5
Index:
P2205[0] : 1st. Drive data set (DDS)
P2205[1] : 2nd. Drive data set (DDS)
P2205[2] : 3rd. Drive data set (DDS)
Details:
See P2201 (Fixed PID Setpoint 1).
Level
2
Level
2
Level
2
Level
2