Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

199

P2016[8]

CI: PZD to BOP link (USS)

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

52:0

P-Group: COMM

Active: Immediately

QuickComm.: No

Max: 4000:0

Selects signals (process data PZD) to be transmitted to serial interface via USS on BOP link

P2012

PZD mapping from parameter P2016

.

.

.

PZD1

ZSW1

PZD2

HIW

PZD3

PZD4

ZSW2

[0]

P2016

[1]
[2]
[3]

[7]

STX
LGE

ADR

PKW

PZD
BCC
ZSW
HIW

r0021

r0052

r0052

r0053

r0053

Start of text
Length
Address
Parameter ID value

Process data
Block check character

USS telegram

USS on BOP link

STX

LGE

ADR

BCC

PKW

PZD

Process data

Parameter

Status word
Main actual value

Index:

P2016[0] : Transmitted word 0
P2016[1] : Transmitted word 1
P2016[2] : Transmitted word 2
P2016[3] : Transmitted word 3
P2016[4] : Transmitted word 4
P2016[5] : Transmitted word 5
P2016[6] : Transmitted word 6
P2016[7] : Transmitted word 7

Example:

P2016[0] = 52.0 (default). In this case, the value of r0052[0] (CO/BO: Status word) is transmitted as 1st
PZD to the BOP link.

Note:

If r0052 not indexed, display does not show an index (".0" ).

Level

3