Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
85
P0732[3]
BI: Function of digital output 2
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
52:7
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source of digital output 2.
Index:
P0732[0] : 1st. Command data set (CDS)
P0732[1] : 2nd. Command data set (CDS)
P0732[2] : 3rd. Command data set (CDS)
Common Settings:
52.0
Drive ready
0 Closed
52.1
Drive ready to run
0 Closed
52.2
Drive running
0 Closed
52.3
Drive fault active
0 Closed
52.4
OFF2 active
1 Closed
52.5
OFF3 active
1 Closed
52.6
Switch on inhibit active
0 Closed
52.7
Drive warning active
0 Closed
52.8
Deviation setpoint/actual value
1 Closed
52.9
PZD control (Process Data Control)
0 Closed
52.A
Maximum frequency reached
0 Closed
52.B
Warning: Motor current limit
1 Closed
52.C
Motor holding brake (MHB) active
0 Closed
52.D
Motor overload
1 Closed
52.E
Motor running direction right
0 Closed
52.F
Inverter overload
1 Closed
53.0
DC brake active
0 Closed
53.1
Act. freq. f_act > P2167 (f_off)
0 Closed
53.2
Act. freq. f_act <= P1080 (f_min)
0 Closed
53.3
Act. current r0027 > P2170
0 Closed
53.4
Act. freq. f_act > P2155 (f_1)
0 Closed
53.5
Act. freq. f_act <= P2155 (f_1)
0 Closed
53.6
Act. freq. f_act >= setpoint
0 Closed
53.7
Act. Vdc r0026 < P2172
0 Closed
53.8
Act. Vdc r0026 > P2172
0 Closed
53.A
PID output r2294 == P2292 (PID_min) 0 Closed
53.B
PID output r2294 == P2291 (PID_max) 0 Closed
P0733[3]
BI: Function of digital output 3
Min: 0:0
CStat:
CUT
Datatype: U32 Unit:
-
Def:
0:0
P-Group: COMMANDS
Active: first confirm
QuickComm.: No
Max: 4000:0
Defines source of digital output 3.
Index:
P0733[0] : 1st. Command data set (CDS)
P0733[1] : 2nd. Command data set (CDS)
P0733[2] : 3rd. Command data set (CDS)
Common Settings:
52.0
Drive ready
0 Closed
52.1
Drive ready to run
0 Closed
52.2
Drive running
0 Closed
52.3
Drive fault active
0 Closed
52.4
OFF2 active
1 Closed
52.5
OFF3 active
1 Closed
52.6
Switch on inhibit active
0 Closed
52.7
Drive warning active
0 Closed
52.8
Deviation setpoint/actual value
1 Closed
52.9
PZD control (Process Data Control)
0 Closed
52.A
Maximum frequency reached
0 Closed
52.B
Warning: Motor current limit
1 Closed
52.C
Motor holding brake (MHB) active
0 Closed
52.D
Motor overload
1 Closed
52.E
Motor running direction right
0 Closed
52.F
Inverter overload
1 Closed
53.0
DC brake active
0 Closed
53.1
Act. freq. f_act > P2167 (f_off)
0 Closed
53.2
Act. freq. f_act <= P1080 (f_min)
0 Closed
53.3
Act. current r0027 > P2170
0 Closed
53.4
Act. freq. f_act > P2155 (f_1)
0 Closed
53.5
Act. freq. f_act <= P2155 (f_1)
0 Closed
53.6
Act. freq. f_act >= setpoint
0 Closed
53.7
Act. Vdc r0026 < P2172
0 Closed
53.8
Act. Vdc r0026 > P2172
0 Closed
53.A
PID output r2294 == P2292 (PID_min) 0 Closed
53.B
PID output r2294 == P2291 (PID_max) 0 Closed
Level
2