beautypg.com

35 faults, alarms, monitoring – Siemens 440 User Manual

Page 207

background image

Issue 01/06

Parameter Description

MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0

207

3.35 Faults,

Alarms,

Monitoring

P2100[3]

Alarm number selection

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: ALARMS

Active: first confirm

QuickComm.: No

Max: 65535

Selects up to 3 faults or warnings for non-default reactions.

Index:

P2100[0] : Fault Number 1
P2100[1] : Fault Number 2
P2100[2] : Fault Number 3

Example:

If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired
reaction in P2101[0] (in this case, set P2101[0] = 3).

Note:

All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g.
overcurrent) cannot be changed from the default reactions.

P2101[3] Stop

reaction

value

Min: 0

CStat:

CT

Datatype: U16 Unit:

-

Def:

0

P-Group: ALARMS

Active: first confirm

QuickComm.: No

Max: 4

Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).

This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.

Possible Settings:

0

No reaction, no display

1

OFF1 stop reaction

2

OFF2 stop reaction

3

OFF3 stop reaction

4

No reaction warning only

Index:

P2101[0] : Stop reaction value 1
P2101[1] : Stop reaction value 2
P2101[2] : Stop reaction value 3

Note:

-

Settings 0 - 3 only are available for fault codes.

-

Settings 0 and 4 only are available for warnings.

-

Index 0 (P2101) refers to fault/warning in index 0 (P2100).

P2103[3]

BI: 1. Faults acknowledgement

Min: 0:0

CStat:

CT

Datatype: U32 Unit:

-

Def:

722:2

P-Group: COMMANDS

Active: first confirm

QuickComm.: No

Max: 4000:0

Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting).

Index:

P2103[0] : 1st. Command data set (CDS)
P2103[1] : 2nd. Command data set (CDS)
P2103[2] : 3rd. Command data set (CDS)

Common Settings:

722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (requires P0704 to be set to 99, BICO)
722.4 = Digital input 5 (requires P0705 to be set to 99, BICO)
722.5 = Digital input 6 (requires P0706 to be set to 99, BICO)
722.6 = Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7 = Digital input 8 (via analog input 2, requires P0708 to be set to 99)


Level

3

Level

3

Level

3