Siemens 440 User Manual
Page 206
Parameter Description
Issue 01/06
MICROMASTER 440 Parameter List
206
6SE6400-5BB00-0BP0
r2090
BO: Control word 1 from CB
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Displays control word 1 received from communication board (CB).
Bitfields:
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulses enabled 0 NO 1 YES
Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES
Bit08 JOG right 0 NO 1 YES
Bit09 JOG left 0 NO 1 YES
Bit10 Control from PLC 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES
Details:
See relevant communication board manual for protocol definition and appropriate settings.
r2091
BO: Control word 2 from CB
Min: -
Datatype: U16 Unit:
-
Def:
-
P-Group: COMM
Max: -
Displays control word 2 received from communication board (CB).
Bitfields:
Bit00 Fixed frequency Bit 0 0 NO 1 YES
Bit01 Fixed frequency Bit 1 0 NO 1 YES
Bit02 Fixed frequency Bit 2 0 NO 1 YES
Bit03 Fixed frequency Bit 3 0 NO 1 YES
Bit04 Drive data set (DDS) Bit 0 0 NO 1 YES
Bit05 Drive data set (DDS) Bit 1 0 NO 1 YES
Bit08 PID enabled 0 NO 1 YES
Bit09 DC brake enabled 0 NO 1 YES
Bit11 Droop enabled 0 NO 1 YES
Bit12 Torque control 0 NO 1 YES
Bit13 External fault 1 0 YES 1 NO
Bit15 Command data set (CDS) Bit 1 0 NO 1 YES
Details:
See relevant communication board manual for protocol definition and appropriate settings.
Level
3