Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
223
P2201[3]
Fixed PID setpoint 1
Min: -200.00
CStat:
CUT
Datatype: Float Unit:
%
Def:
0.00
P-Group: TECH
Active: Immediately
QuickComm.: No
Max: 200.00
Defines Fixed PID Setpoint 1
There are three options available for selection of the PID fixed setpoints:
1. Direct
selection
2. Direct selection + ON command
3. Binary coded selection + ON command
1. Direct selection (P0701 - P0706 = 15):
-
In this mode of operation, 1 digital input selects one PID fixed setpoint.
-
If several inputs are active together, the selected setpoints are summed.
-
E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6.
2. Direct selection + ON command (P0701 - P0706 = 16):
-
In this mode of operation the PID fixed setpoints are combined with an ON command.
-
Description as for 1), except that this type of selection issues an ON command concurrent with any
setpoint selection.
-
If several inputs are active together, the selected setpoints are summed.
-
E.g.: PID-FF1 + PID-FF2 + PID-FF3 + PID-FF4 + PID-FF5 + PID-FF6.
3. Binary coded selection + ON command (P0701 - P0706 = 17):
-
Using this method to select the fixed PID setpoint (FF-PID) allows you to choose up to 16 different
PID setpoints.
-
The setpoints are selected according to the following table:
Index:
P2201[0] : 1st. Drive data set (DDS)
P2201[1] : 2nd. Drive data set (DDS)
P2201[2] : 3rd. Drive data set (DDS)
Example:
DIN4
DIN3
DIN2
DIN1
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
Binary coded selection :
P1001
0 %
P1002
P1003
P1004
P1005
P1006
P1007
P1008
P1010
P1011
P1012
P1013
P1014
P1015
P1009
PID - FF0
PID - FF1
PID - FF2
PID - FF3
PID - FF4
PID - FF5
PID - FF6
PID - FF7
PID - FF8
PID - FF9
PID - FF10
PID - FF11
PID - FF12
PID - FF13
PID - FF14
PID - FF15
Level
2