Siemens 440 User Manual
Page 215
Issue 01/06
Parameter Description
MICROMASTER 440 Parameter List
6SE6400-5BB00-0BP0
215
r2169
CO: Act. filtered frequency 3
Min: -
Datatype: Float Unit:
Hz
Def:
-
P-Group: ALARMS
Max: -
Filtered frequency for monitoring behind first-order lowpass filter.
-
|f_act| > f_1 (see P2155)
-
|f_act| > f_2 (see P2157)
-
|f_act| > f_3 (see P2159)
P2170[3]
Threshold current I_thresh
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
%
Def:
100.0
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 400.0
Defines threshold current in [%] relative to P0305 (rated motor current) to be used in comparisons of I_act
and I_Thresh as illustrated in the diagram below.
0
1
Threshold current
0.0 ... 400.0 [%]
P2170.D (100.0)
Delay time current
0 ... 10000 [ms]
P2171.D (10)
I_act
| I_act | > I_thresh
|I_act| > I_thresh
0 T
r0053 Bit03
Index:
P2170[0] : 1st. Drive data set (DDS)
P2170[1] : 2nd. Drive data set (DDS)
P2170[2] : 3rd. Drive data set (DDS)
Note:
This threshold controls bit 3 in status word 3 (r0053).
P2171[3]
Delay time current
Min: 0
CStat:
CUT
Datatype: U16 Unit:
ms
Def:
10
P-Group: ALARMS
Active: Immediately
QuickComm.: No
Max: 10000
Defines delay time prior to activation of current comparison.
Index:
P2171[0] : 1st. Drive data set (DDS)
P2171[1] : 2nd. Drive data set (DDS)
P2171[2] : 3rd. Drive data set (DDS)
Details:
See diagram in P2170 (threshold current I_thresh)
Level
2
Level
3
Level
3