P1442[3]
Filter time for act. speed
Min: 0
CStat:
CUT
Datatype: U16 Unit:
ms
Def:
4
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 32000
Sets time constant of PT1 filter to smooth actual speed of speed controller.
Index:
P1442[0] : 1st. Drive data set (DDS)
P1442[1] : 2nd. Drive data set (DDS)
P1442[2] : 3rd. Drive data set (DDS)
r1445
CO: Act. filtered frequency 2
Min: -
Datatype: Float Unit:
Hz
Def:
-
P-Group: CONTROL
Max: -
Displays filtered actual frequency at speed controller input.
P1452[3]
Filter time for act. freq (SLVC)
Min: 0
CStat:
CUT
Datatype: U16 Unit:
ms
Def:
4
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 32000
Sets time constant of PT1 filter to filter the frequency deviation of speed controller in operation mode SLVC
(sensorless vector control).
Index:
P1452[0] : 1st. Drive data set (DDS)
P1452[1] : 2nd. Drive data set (DDS)
P1452[2] : 3rd. Drive data set (DDS)
P1460[3]
Gain speed controller
Min: 0.0
CStat:
CUT
Datatype: Float Unit:
-
Def:
3.0
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 2000.0
Enters gain of speed controller.
Precontrol
Freq. setpoint
r1438
r1084
–
Kp
Tn
P1460 P1462
r0064
Torque
setpoint
P1496 P0341 P0342
P1442
Act. frequency
from encoder
r0063
r1170
–
P1492
P1489
P1488
Droop
r1490
150 ms
r1518
0
1
0
r0079
r1508
*) only active, if pre-control is enabled
(P1496 > 0)
*)
Index:
P1460[0] : 1st. Drive data set (DDS)
P1460[1] : 2nd. Drive data set (DDS)
P1460[2] : 3rd. Drive data set (DDS)
P1462[3]
Integral time speed controller
Min: 25
CStat:
CUT
Datatype: U16 Unit:
ms
Def:
400
P-Group: CONTROL
Active: Immediately
QuickComm.: No
Max: 32001
Enters integral time of speed controller.
Index:
P1462[0] : 1st. Drive data set (DDS)
P1462[1] : 2nd. Drive data set (DDS)
P1462[2] : 3rd. Drive data set (DDS)